etting the minimum and the maximum power of the boiler
1.
Check that the supply pressure and dynamic working pressure to
t
he gas valve is a minimum of 20 mbar for natural gas.
2. To do this, loosen the screw “A”.
Fit the pipe of the pressure gauge to the inlet pressure
connection of the gas valve
“B” and check for the correct
standing pressure, then operate the appliance and check for the
correct working pressure.
When you have completed this operation, replace the screw
“A”
securely into its housing to seal off the gas (check for tightness).
3. To check the pressure supplied by the gas valve to the burner,
loosen the screw “C”. Fit the pipe of the pressure gauge to the
pressure outlet test point of the gas valve
“D”.
Disconnect the compensation pipe “D1” either from the gas
valve or from the sealed chamber.
4. Turn the On/Off knob to “ON” position -green light- and ensure
that the hot water temperature control knob is set to maximum.
Turn on the boiler by running a hot water tap.
Adjust the 10mm nut “E” on the modureg to set the maximum
gas pressure, turn the nut clockwise to increase and anti
clockwise to decrease the pressure until the required pressure is
achieved (see
TA
BLE
A Page 35).
5. To set the minimum power, disconnect a supply terminal “F1”
from the modureg and adjust screw “F” (ensure that the 10mm
nut is held in position). Turn the screw clockwise to increase the
pressure and anti-clockwise to decrease the pressure (displayed
on the pressure gauge) corresponding to the minimum power
(see
TABLE A Page 35).
6. When you have completed the above operations, turn off the hot
water tap, reconnect the supply terminal to the modureg on the
gas valve, reconnect the compensation pipe and replace the cap
on the screw of the modureg.
36
IMPORTANT!
Whenever you disassemble and reassemble the gas
connections, always check for leaks using a leak
detection fluid.
4.2 ADJUSTING THE GAS PRESSURES