Ariston GENUS Technical Information Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 86
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
35
4. GAS ADJUSTMENTS
CATEGORY II2H3+ Methane Gas
G
20
Liquid Butane Gas
G
30
Liquid Propane Gas
G
31
L
ower Wobbe Index (15°C;1013mbar) MJ/m
3
h
Nominal Delivery Pressure mbar
M
inimum Delivery Pressure mbar
4
5.67
20
2
0
8
0.58
29
2
8
8
0.58
37
3
6
0.70
-
--
2.86 - 0.85
35.6 - 6.8
0.70
---
2.17 - 0.93
36.0 - 7.1
0.70
---
2.45 - 0.93
36.0 - 7.0
0.70
---
1
.89 - 0.87
2
9.0 - 5.5
0.70
---
2.21 - 0.95
27.5 - 5.4
0.70
---
2.48 - 0.95
28.0 - 5.4
1.30
2.54 - 1.16
-
--
7
.5 - 1.7
1.30
2.96 - 1.27
---
9.5 - 1.8
1.30
3.33 - 1.27
---
12.0 - 1.8
microGENUS HE 24 MFFI
Main Burner: n. 14 jets (ø) mm
Consumption (15°C; 1013mbar) max - min m
3
/h
C
onsumption (15°C; 1013mbar) max - min Kg/h
Gas Burner Pressure
m
ax - min mbar
microGENUS HE 28 MFFI
Main Burner: n. 14 jets (ø) mm
Consumption (15°C; 1013mbar) max - min m
3
/h
Consumption (15°C; 1013mbar) max - min Kg/h
Gas Burner Pressure
max - min mbar
microGENUS HE 32 MFFI
Main Burner: n. 14 jets (ø) mm
Consumption (15°C; 1013mbar) max - min m
3
/h
Consumption (15°C; 1013mbar) max - min Kg/h
Gas Burner Pressure
max - min mbar
The boiler can be converted to use either methane (natural)
gas (G20) or L.P.G. (G30 - G31) by an Authorised Service
Centre.
The operations that must be performed are the following:
1. Replace the jets on the main burner (see Table A);
2.
Adjust the maximum and minimum thermal capacity values for
the boiler
(see Table A and Section 4.2 Adjusting the Gas
Pressures)
;
3. Adjust the maximum thermal power setting (see tables in
section 4.3 and FIG. 4.1 page 35);
4.
Adjust the soft-light f
eature
(see
T
ab
le A for recommended
pressure and Fig. 4.1
see page 35);
5. Adjust the ignition delay feature for the heating system by
adjusting the Jumper as indicated in Section 2.16
(FIG. 2.30). It
can be tur
ned on or off
.
4.1 CHANGING THE TYPE OF GAS
CATEGORY
II2H3+
Methane
Gas
G20
Liquid
Butane
Gas
G30
Liquid
Propane
Gas
G31
Soft-light
Pressure (mbar)
24 kW Model
28 kW Model
32 kW Model
5.0
5.5
5.5
12.0
12.0
12.0
12.0
12.0
12.0
TABLE A
SOFT LIGHT PRESSURES
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 85 86