Warning
The exhaust gas ducts must not be in contact with or close to
inflammable material and must not pass through building
structures or walls made of inflammable material.
When replacing an old appliance, the flue system must be
changed.
Important
Ensure that the flue is not blocked.
Ensure that the flue is supported and assembled in
accordance with these instructions.
2.9.1 FITTING THE COAXIAL FLUE
(Ø 60 / 100 HORIZONTAL)
* slope 5 mm per metre
150 mm
* slope
Installation without extension
Installation with extension
FIG. 2.10
FIG. 2.11
118
Level
Level
CONTENTS:
1
X SI
LICONE
O-RI
NG
(60mm)
1X ELBOW (90
O
)
2
X WALL SEALS (INTERNAL & EXTERNAL)
1
X FLUE PIPE INCLUDING TERMINAL (1 METRE - 60/100)
1
X FLUE CLAMP
2X SCREWS
1x Seal
Once the boiler has been positioned on the wall, insert the elbow
into the socket and rotate to the required position. NOTE: It is
possible to rotate the elbow 360
o
on its vertical axis.
Using the flue clamp, seals and screws supplied (Fig 2.12)
secure the elbow to the boiler.
The 1 metre hor
iz
ontal flue kit (3318073) supplied is suitab
le f
or
an exact
X dimension of 823 mm.
Measure the distance from the face of the external wall to the
face of the flue elbow
(X - Fig 2.9), subtract 48 mm from this
measurement, y
ou now have the total length of flue required
(including the ter
minal), this figure m
ust no
w be subtr
acted from
907mm, you now have the total amount to be cut from the plain
end of the flue.
Cut the flue to the required length ensuring that the distance
betw
een the inner and the outer flue is maintained
(Fig 2.12
)
.
e
.g.
X = 508mm - 48mm = 460mm
823 - 460 = 363mm (Length to be cut from the plain end of
the flue).
Once cut to the required length, ensure that the flue is free from
burrs and reassemble the flue. If fitting the flue from inside of the
building attach the grey outer wall seal to the flue terminal and
push the flue through the hole, once the wall seal has passed
through the hole
, pull the flue back until the seal is flush with the
w
all.
Alter
nativ
ely
, the flue can be installed from outside of the
building, the grey outer seal being fitted last.