Installation
Instructions
Type C Boilers
G.C.N: 41-116-05
LEAVE THESE INSTRUCTIONS
WITH THE END-USER
Country of destination: GB
Page view 0
1 2 3 4 5 6 ... 59 60

Summary of Contents

Page 1 - G.C.N: 41-116-05

InstallationInstructionsType C BoilersG.C.N: 41-116-05LEAVE THESE INSTRUCTIONSWITH THE END-USERCountry of destination: GB

Page 2 - TABLE OF CONTENTS

L = Sum of the total length of exhaust + air intake piping.10ExhaustTypeC12 (xx)C32 (xx)C42 (xx)Restrictorø 41 mmL min = 0.5 mL max = 1 mMaximumExten

Page 3 - 1.1 GENERAL INSTRUCTIONS

2.11 ELECTRICAL DIAGRAM11FIG. 2.12Legend: A - On/Off SwitchB - On/Off L.E.D.C - Heating SwitchD - Heating L.E.D.E - Reset ButtonF - Ignition Failure

Page 4 - 2. INSTALLATION

121234567891011121314151617LEGEND:1. Fan2. Main heat exchanger3. Overheat thermostat 4. Burner 5. Ignition electrodes6. Detection electrode7. Regulati

Page 5

133. D.H.W. STORAGECYLINDERThe microSYSTEM can be connected to a storage cylinder (both open-vented andunvented) for the production of domestic hot wa

Page 6 - IEW OF THE BOILER CONNECTIONS

14Technical Data Capacity Coil C.H.W. D.H.W. Max Heating Heat IossSurface Flow/rate Flow/rate OutputMODEL It. m2m3/h It/h kW kWh/24hContract STI 125 I

Page 7 - RESIDUAL HEAD OF THE BOILER

15MTS (GB) Limited support the initiative. Within the information pack you willfind a copy of the logbook. It is important th

Page 8 - FIG. 2.5

B45In order to access the inside of the boiler, it is necessary tounscrew the fastening screws “A” of the control panel located onthe lower part of th

Page 9 - COAXIAL SYSTEMS

17The flue connector has two apertures, readings can be taken forthe temperature of the combustion by-products and of thecombustion air, as well as of

Page 10 - 2.10 ROOM THERMOSTAT

The boiler is fitted with the following devices (see section 4.2 for references).1 - IGNITION FAILURE:This indicates ignition failure when a flame is

Page 11 - FIG. 2.12

It is recommended that the following inspections be carried out on the boiler atleast once a year:1 - Check the seals for the water connections; repla

Page 12

This manual is an integral and essential part of the product. It should be kept with theappliance so that it can be consulted by the user and our auth

Page 13 - CYLINDER

Manufacturer: Merloni TermoSanitari SpA - ItalyCommercial subsidiary: MTS (GB) LIMITEDMTS BuildingHughenden AvenueHigh WycombeBucks HP13 5FTTelephone:

Page 14 - TABLE 3.1

ServicingInstructionsType C BoilersG.C.N: 41-116-05LEAVE THESE INSTRUCTIONSWITH THE END-USERCountry of destination: GB

Page 15 - PRIORITY KIT

21. SERVICING INSTRUCTIONS1.1 REPLACEMENT OF PARTS1.2 TO GAIN GENERAL ACCESS- Removing the front panel- Removing the sealed chamber front cover- Remov

Page 16

2. The control panel moves downward and when pulled forward,rotates on two lateral hinges; the panel stays in a semi-horizontal position, which allows

Page 17 - IG.4.1) - the

41.2.2 Removing the sealed chamber front cover1. Remove the screws “C” (FIG. 1.6);2. Lift the sealed chamber front cover from the locating pins(FIG. 1

Page 18 - 4.8 DRAINING THE SYSTEM

1.3.3 Removing the electrodesBefore carrying out this procedure, unscrew and slide theburner forward (see previous section).1. Remove rubber gasket “G

Page 19 - TABLE 5.1

63. Remove screw “H” (FIG. 1.14);4. Gently slide the electrode downward (FIG. 1.15).To replace, repeat the steps in reverse order, payingparticular at

Page 20 - - Stampa: bieffe RECANATI

1. Disconnect electrical connections “N” and silicon pipe “O”(FIG.1.22);2. Remove screw “P” and remove the fan collar clamp “Q”(FIG.1.23);3. Remove sc

Page 21 - Servicing

81.4 SERVICING AND REMOVALOF THE GAS VALVE1.4.1 Setting the gas pressures123ABCFDSetting the maximum power of the boiler1. Check that the supply press

Page 22 - TABLE OF CONTENTS

915 RFFI1.63 208.53.33.3--------------1.21 Kg/h------ Kg/h22.1 mbar---- mbar28 mbar1.19 Kg/h------ Kg/h28.8 mbar---- mbar37 mbar8 x 1.30 8 x 0.778 x

Page 23 - 1. SERVICING INSTRUCTIONS

31.1 GENERAL INSTRUCTIONSRead the instructions and recommendations in these Installation Instructionscarefully to ensure proper installation, use and

Page 24

10FIG. 1.28FIG. 1.29UVV1.4.3 Removing the gas valveImportant! Before removing the gas valve, ensure the gassupply is turned off.1. Disconnect all the

Page 25 - IG. 1.9);

111. 5. 2 Removing the safety valve1. Loosen nut “Y” (FIG. 1.33);2. Disconnect the discharge pipe work from below theboiler;3. Unscrew and remove the

Page 26 - IG. 1.17);

121.5.4 Removing the pump1. Remove the U-clips “ A1” and “B1” (FIG. 1.36);2. Remove the retaining clip “C1” (FIG. 1.37);3. Release the nut “D1” (FIG.

Page 27 - IG.1.25)

131.5.6 Removing the expansion vessel1. Release nuts “H1” and remove the gas pipe (FIG. 1.44);2. Release nut “I1” (FIG. 1.45);3. Remove lock-nut “J1”

Page 28 - ABLE A page 9)

141.5.6 Removing the overheat thermostat1. Disconnect the overheat thermostat electricalconnections “K1” (FIG. 1.48);2. Then remove the thermostat fro

Page 29

151.6.2 Removing the P.C.B.s1. Isolate electricity;2. Remove the screws “O1” (FIG. 1.56);3. Separate the facia panel from the rear of the controlpanel

Page 30 - IG. 1.27);

16B0632. FAULT FINDINGPRELIMINARY CHECKSMAKE SURE THAT:ISTHE SUPPLYL.E.D. ILLUMINATED?ISTHE L.E.D.ILLUMINATED?NONONOYESNO1 - CHECK THE FUSES2 - CHECK

Page 31 - IG. 1.32);

17B063IS THE PUMPRUNNING?NOYESPOWER TOTHE PUMP?1 - CHECK THE OPERATIONOF THE PUMP2 - RELEASE/REPLACE THEPUMP1 - CHECK THE PUMP CABLE2-CHECK/REPLACE P.

Page 32

18B063IS THE BURNERALIGHT?YESNOYESYESBOILERWORKING?YESNONONONOYES5-CHECK/REPLACE P.C.B. (CBM2)4-CHECK/REPLACE P.C.B. (CBM2)4 - CHECK/REPLACEP.C.B. (CB

Page 33

19B0633. ELECTRICALDIAGRAMSSE011ALEGEND:A - On/Off SwitchB - On/Off L.E.D.C - Heating SwitchD - Heating L.E.D.E - Reset ButtonF - Ignition Failure (Lo

Page 34

4The technical information and instructions provided herein below are intended for theinstaller so that the unit may be installed correctly and safely

Page 36 - (FLOW-CHARTS)

21B063MODELS CHARACTERISTICS SERIAL NO:VALIDITYREF.MICROSYSTEM 10 RFFI METHANE 2320021100001 AMICROSYSTEM 10 RFFI LPG 2320021100001 BMICROSYSTEM 15 RF

Page 37 - 1 - REPLACE THE FAN

22B063998616573521573520570760998612573528998447569390998627999542574279999474998809999476998424998836999578999499999245998517998484997182999538998624

Page 39 - DIAGRAMS

23 99 84 1570 000 - Manufacturer: Merloni TermoSanitari SpA - ItalyCommercial subsidiary: MTS (GB) LIMITEDMTS BuildingHughenden AvenueHigh WycombeBuck

Page 40

UsersManual

Page 41 - PARTS LIST

2Dear Customer,Thank you for choosing an ARISTON boiler.We guarantee that your boiler is a reliableand technically sound product.This User's Manu

Page 42

TABLE OF CONTENTS1. GENERAL INFORMATION page 4Technical Information page 5Control Panel page 62. OPERATING INSTRUCTIONS page 73. USEFUL INFORM

Page 43

41. GENERAL INFORMATIONMTS (GB) Limited support theinitiative. Your installer will give you, andshow you how to use, a logbook which willgive you impo

Page 44

TECHNICAL INFORMATION5GENERAL DATAHeating input max-minHeating output max-minEfficiency at Maximum Thermal Capacity (see Installation Instructions)CEN

Page 45

For safety purposes, have a competent person carefully check the electrical systemin the property, as the manufacturer will not be held liable for dam

Page 46

6CONTROL PANEL10 RFFI / 15 RFFI21 RFFI /28 RFFIFR011A

Page 47

2. OPERATING INSTRUCTIONSCAUTIONInstallation, start-up, adjustments andmaintenance must be performed by acompetent person only, in accordancewith the

Page 48 - 1. GENERAL INFORMATION

8HELPFUL SUGGESTIONSTo get the most out of your boiler, we haveprovided you with some useful advice onproper use and maintenance:- Periodically check

Page 49 - TECHNICAL INFORMATION

Ignition procedure Push the button “A” the green L.E.D. “B”will illuminate indicating that the boiler issupplied with electricity.Push the button “C”

Page 50 - 21 RFFI /28 RFFI

10EFThe centralised electronic control unit willignite the burner, without any manualintervention but in response to the requestfor heating. If, after

Page 51 - OPERATING INSTRUCTIONS

Turning off central heatingTo turn off the central heating, push the “C”button and the green L.E.D. ”D” will go off.The boiler will remain electricall

Page 52 - PRACTICAL TIPS

12Turning off the boilerTo turn the boiler off, push the button “A”the respective green L.E.D. “B” will go off.Close the gas cock located under the bo

Page 53 - Ignition procedure

to allow the exchanger to cool down, thenpress and release the reset button “E”.If this situation occurs frequently, contact anAuthorised Service Cent

Page 54 - Adjusting the heating

14the correct level the boiler will igniteautomatically. If there are frequent drops inpressure within the system, have a plumbercheck the heating sys

Page 55 - External (room) thermostat

the other, one of our Authorised ServiceCentres should be contacted.6. TIME CLOCKA time clock for central heating is availableas an accessory kit and

Page 56 - Boiler shutdown situations

6The boiler operates with alternating current, as indicated in thetechnical information table in section 7, where the maximumabsorbed power is also in

Page 57 - Shutdown due to overheating

Cod. 23 99 84 1548 112Manufacturer: Merloni TermoSanitari SpA - ItalyCommercial subsidiary: MTS (GB) LIMITEDMTS BuildingHughenden AvenueHigh WycombeBu

Page 58 - Temporary shutdown due to

7CENTRAL HEATINGDetailed recommendations are given in BS 6798:1987 and BS 5449-1:1990, thefollowing notes are given for general guidance.PIPE WORK:Cop

Page 59 - 5. CHANGE OF GAS TYPE

8Ø 60/100 mmFIG. 2.6ABCDEFGJKHILGFThe boiler is designed to be connected to a coaxial flue discharge system.2.9 FLUE CONNECTIONSFLUE SYSTEMThe provisi

Page 60

Ø 80 mmIn addition, it is also possible to use a split (twin pipe) system byfitting a special adaptor to the flue connector and using theaperture for